Technical parameters
Parameter
Model
TH6935-200
TH6980-120
TH69200-50
TH69360-30
TH69500-20
TH69750-12
TH691000-10
Rated output
Voltage
35V
80V
200V
360V
500V
750V
1000V
The current
200A
120A
50A
30A
20A
12A
10A
Power
3000W
Efficiency
≤ 92%
≤ 92%
≤ 92%
≤ 93%
≤ 93%
≤ 93%
≤ 93%
Load adjustment rate
Voltage
≤ 0.05%FS ( 0- 的Load adjustment rate)
The current
≤ 0.15%FS ( 0- Δ UDC 的Load adjustment rate)
Power adjustment rate
Voltage
≤ 0.02%FS ( ± 10% Δ UAC Enter )
The current
≤ 0.05%FS ( ± 10% Δ UAC Enter )
Setpoint resolution
Voltage
10mV
10mV
10mV
10mV
10mV
10mV
10mV
The current
10mA
10mA
10mA
10mA
10mA
10mA
10mA
Read back value resolution
Voltage
10mV
10mV
10mV
10mV
10mV
10mV
10mV
The current
10mA
10mA
10mA
10mA
10mA
10mA
10mA
Programming accuracy
(25 ℃± 5 ℃ )
Voltage
≤± (0.05%+0.04%FS)
The current
≤± (0.15%+0.1%FS)
Power
≤± 0.8%FS
Read back accuracy
(25 ℃± 5 ℃ )
Voltage
≤± (0.05%+0.04%FS)
The current
≤± (0.15%+0.1%FS)
Power
≤± 0.8%FS
Ripple and Noise
RMS
(20Hz-300kHz)
10mVrms
10mVrms
20mVrms
40mVrms
50mVrms
75mVrms
100mVrms
P-P
(20Hz-2MHz)
75mVpp
100mVpp
175mVpp
250mVpp
325mVpp
500mVpp
650mVpp
Rise time
No load 10%-
≤ 2ms
Rise time
满载 10%-90%
≤ 30ms
Protection function
OTP,OVP, OCP, OPP, PF
Isolation withstand voltage
1000VDC (Output to the earth)
Master-slave parallel
Through the True Lord - From operation, up to -- can be connected 10 tform product (via shared bus --) )
Protect
OTP, OVP, OCP, OPP, PF
Store
10 组工作模式; 50 A sequence, each group 20 Step
Analog interface
Specifications
Built-in 15- Needle D-Sub Female plug, electrical isolation
Signal range
0~5V Or 0~10V( Switchable )
U / I / P Accuracy
0~10V: ≤ 0.2%FS 0~5V: ≤ 0.4%FS
Power supply Power
Phase number
1ph+N+PE
Voltage
220VAC ± 10%
Frequency
45~66Hz
Power因数
≥ 0.99
The working environment
Indoor type; Operating temperature: 0~50 ℃, Humidity: <80%, No condensation, Storage temperature: -20~70 ℃,
Altitude: <2000m
Size W × H × D(mm)
482mm × 88mm × 455mm (W × H × D) Standard chassis, height 2U
The weight
13.5kg