Product specifications: Fluke 707 loop calibrator
Technical index | ||
Current measurement | The range of | 0 to 24 mA |
Resolution | 0.001 mA | |
Precision | The reading is 0.015percent 2 LSD | |
Current output | The range of | 0 to 20 mA or 4 to 20 mA |
Precision | The reading is 0.015percent 2 LSD | |
Driving ability | 1200Ω 950Ω -- in HART mode at 20 mA | |
Current simulation | The range of | 0 to 20 mA or 4 to 20 mA |
Precision | The reading is 0.015percent 2 LSD | |
External loop voltage requirements | 12-30 V | |
Loop power supply | mA was measured at 24 V | |
Voltage measurement | The range of | 0 to 28 V direct current |
Resolution | 1 mV | |
Precision | The reading is 0.015percent 2 LSD | |
Environmental indicators | ||
Operating temperature | -10°c - 55°c | |
Storage temperature | -30°c - 60°c | |
Humidity (no condensation) | 0 - 90%(0°C - 35°C);0 - 70%(35°C - 55°C | |
Temperature coefficient | -10 °C 至 18 °C,28 °C 至 55 °C,The range of的 ±005%/°C | |
Safety specifications | ||
Security | CSA C22.2 010.1:1992 | |
Electromagnetic compatibility (EMC) | en50082 - 1:20 92和en55022:1994 | |
Maximum voltage | 30 V | |
Mechanical and general specifications | ||
Size | 152 x 70 x 41 mm | |
The weight of | 224 g (340 g, including holster) | |
Battery | 一节 9 V 碱性Battery | |
Warranty period | Three years | |
Shock and vibration | Specification for Level 2 instrumentation according to MIL-T-28800 (military specification) | |
显示电流和The range of比例 ( %) | There is | |
Automatic step, automatic slope | There is | |
Span check | There is |